Persistent high biological counts in a closed-loop cooling system
a. despite dosing isothiazolone, glutaraldehyde, and a biodispersant.
2. Answer First
a. You’re likely dealing with an entrenched biofilm that’s resisting standard treatments. A combined shock program—high-dose biodispersant + rotated biocide + mechanical filtration—should be implemented immediately.
3. Likely Reasons for Persistent Biological Contamination
a. Chemical Ineffectiveness
i. Biocide Suboptimal
Biocide dose – low
Contact time – insufficient
pH – High or low
Temperature
Dilutions from leaks
ii. Bio dispersant Suboptimal
Product selection in combination with biocide
Poor penetration
Low Dose
b. BioFilm Existing biofilm shedding microbes
Low flow low sheer areas
c. Mechanical system Dead legs
Poorly maintained filters – recolonization
Sand filters
4. Chemical and pH
pH Glute ½ life Iso ½ life Difference
8.0 30 – 45 days 20 – 30 days Both stable – Glute is more durable
9.0 3 – 5 2 – 3 Both start to degrade – Iso faster
10 8 – 12 Hrs 1 – 3 Hrs
10.5 1 – 3 < 1
a. Glutaraldehyde degrades via aldol condensation and polymerization, forming non-biocidal polymers that may contribute to fouling, especially at pH >9.5.
b. Isothiazolone degrades via alkaline hydrolysis, breaking the active ring structure and yielding non-biocidal fragments—rapid and irreversible above pH 9.
- Dosage Review:
- Isothiazolone: 10–25 ppm active (higher if slug dosing weekly)
- Glutaraldehyde: 50–200 ppm active (often 100 ppm slug for control)
- Biodispersant: follow manufacturer dose; if it’s <100 ppm, consider increasing.
6. Conduct a Biofilm Penetration Strategy
- Apply a shock dose of dispersant (e.g., 200 ppm non-ionic or amphoteric dispersant) with high-dose oxidizing or non-oxidizing biocide.
i. Let circulate for 6–12 hours.
ii. Filter heavily.
- Consider temporary installation of a side stream filter (1–5 micron) to capture biomass slough-off.
8. Inspect and Eliminate Stagnation Points
- Audit the loop for dead legs, idle branches, or bypasses.
- If present, retrofit with continuous flow or flush valves.
- Confirm minimum velocity (~3 fps) is maintained in all parts of the loop.
11. Switch or Rotate Biocides
- Microbial resistance can build to repeated treatments. Try this:
i. Replace glutaraldehyde with DBNPA or THPS, both effective in closed loops.
12. Confirm Test Accuracy
- Ensure microbial monitoring uses both culture-based (dip slides, HPC) and ATP-based testing for more insight.
- Take samples from multiple representative points—not just the supply header.
13. Mechanical Cleaning if Needed
- If counts remain high after chemical cleaning, consider mechanical cleaning (e.g., pigging or flushing loop segments).
- Review loop filters—clean or replace them frequently during biocide treatment cycles.
14. Longer-Term Improvements
Action | Purpose |
Install permanent side-stream filtration | Prevent long-term fouling and remove residual biofilm slough |
Use a real-time microbial sensor (e.g., ATP probe) | Continuous monitoring vs. batch testing |